An ESPHome external component that reads and controls a Daikin VRV system through its F1F2 bus (DIII-NET), the two-wire bus the outdoor unit, the indoor units and a central controller such as the Daikin iTM share. It runs on a P1P2MQTT bridge and shows up in Home Assistant as one device per indoor unit, with a climate entity per remote-control group.
This component is not made or supported by Daikin. Daikin does not publish the DIII-NET protocol: everything here was worked out from bus logs of one system (see docs/protocol.md). Read the known limitations before you let it write to your bus.
Per remote-control group (configured on the group master):
| Entity | What it does |
|---|---|
| Climate | Off, heat, cool, fan only; fan auto/low/medium/high; setpoint 16-32 °C in whole degrees. Auto and dry set elsewhere are shown, but can't be set from here. One command switches the whole group. |
| Airflow direction (select) | Swing, or a fixed flap position from Position 0 (horizontal) to Position 4 (down). |
| Setpoint, Fan, Mode (sensors) | The group's settings as the bus reports them. |
| Remote controller temperature | The sensor in the wired remote. The climate's current temperature uses it when there is one. |
| Liquid / gas pipe temperature | The indoor coil's refrigerant pipes. |
| Setting commands, Write budget left (diagnostic) | Setting commands seen on the bus for this group (from any controller), and how many more this bridge may send now (see Controlling units). |
Per indoor unit:
| Entity | What it does |
|---|---|
| Temperature | Return air at the unit. |
| Power, Mode | As the unit reports them. |
| Heat demand | The unit's own thermostat asks for heat (status bit 0x20). |
| Outlets 1+3, Outlets 2+4 (selects) | Per-outlet flap setting of 4-way cassettes, by pair of opposite outlets: Normal or Fixed (0). Write-only (see limitations). |
For the system:
| Entity | What it does |
|---|---|
| Outdoor temperature | Outdoor air at the outdoor unit. |
| Evaporating / condensing temperature | Te and Tc of the refrigerant circuit. |
| Discharge temperature per outdoor module | Compressor discharge (hypothesis). |
| Compressor | Running or not. |
| Defrost or oil return | An outdoor module in sub-state 07, a recurring 9-minute operation that looks more like oil return than defrost (hypothesis). |
| System clock | The VRV's own clock. The bus sends it every 10 minutes; the bridge counts the minutes in between, and stops counting when no update has come for 15 minutes, so a lost bus shows as a clock that stands still. |
| Diagnostics | Bus frames OK / with errors, write queue, last bus command, compressor speed, current, compressor and fan steps (partly guessed). |
A Daikin hydrobox on the same bus gets its temperature, power, heat demand and a heat demand step (0-15) sensor, and a climate that switches it on and off and between heat and cool. It has no target temperature: the leaving-water setpoint isn't decoded.
Switches: Bus writes enabled (off = read-only), ATmega programming (see
docs/atmega.md) and Raw logging (only with raw_mqtt). A button
restarts the ATmega.
A group master in Home Assistant: the climate, airflow and outlet selects, the group's sensors and the write budget.
A dashboard built from these entities, with a climate and a temperature history per group. The dashboard itself isn't part of this repository.
The system view of the same dashboard: outdoor unit temperatures and compressor state, and the bridge's switches and bus diagnostics.
A P1P2MQTT bridge v1.2 or v1.3 (ESP8266, ATmega328P and a MAX22088 bus transceiver), connected to the F1F2 terminals of an indoor or outdoor unit. The bridge is powered from the bus.
The ATmega runs Arnold Niessen's P1P2Monitor firmware, F1F2 build (tested with v0.9.56 and v0.9.58), and does the bus I/O. The ESP8266 runs ESPHome with this component instead of the stock P1P2MQTT bridge firmware. See docs/hardware.md for the pins, the first install and how to go back to the stock firmware.
Start from example.yaml, a complete config for a bridge with two groups.
Copy secrets.yaml.example to secrets.yaml next to it and fill
it in.
It loads the component and the packages from this repository:
external_components:
- source: github://casdr/esphome-daikin-f1f2@main
components: [daikin_diii]The component uses ESPHome internals and is tested with ESPHome 2026.10.2 (pinned in the Pipfile). A newer ESPHome may need changes.
The first install on a bridge that still runs the stock firmware goes through the stock web page; see docs/hardware.md.
Describe your system with the ESPHome packages in packages/: the bridge once, then one package per indoor unit.
packages:
daikin:
url: https://github.com/casdr/esphome-daikin-f1f2
ref: main
files:
- path: packages/bridge.yaml
- path: packages/group-master.yaml # 1-01 has the wired remote
vars: {id: "01", name: Daikin 1-01, area: area_living}
- path: packages/unit.yaml # 1-00 follows 1-01
vars: {id: "00", group: "01", name: Daikin 1-00, area: area_living}| Package | For |
|---|---|
bridge.yaml |
The bridge hardware, the bus, the system-wide entities, the switches and the research actions. Once. |
group-master.yaml |
The unit with the wired remote, or a unit on its own: climate, airflow, setpoint, fan, the unit's own sensors. |
unit.yaml |
A member of a group: temperature, power, mode, heat demand. |
remote-sensors.yaml |
Remote and pipe temperatures of a group master. Needs its b1_index. |
outlets.yaml |
The two outlet selects of a 4-way cassette. |
hydrobox.yaml |
A hydrobox: temperature, power, heat demand. |
id is the unit's address as two hex digits. Units are numbered on the bus as 1-00,
1-01 … 2-00: id: "00" is 1-00, id: "10" is 2-00. You can also write the
daikin_diii: units: list and the entities by hand; docs/configuration.md
lists every option.
The bridge logs a warning when the bus says a unit is a group master and your table says it isn't, or the other way round.
docs/configuration.md explains every option and entity, and how to find the addresses, groups and B1 indexes of your system from a bus log.
Writing is off until you turn on Bus writes enabled. With it on, the climate, airflow and outlet entities send commands on the bus, as a second central controller:
- Commands use source address
0x30. The component refuses0x0A, the iTM's own address: using it makes the iTM raise error MC (address duplicated). - Every setting command is stored in the indoor unit's non-volatile memory, which wears out. Daikin limits control commands to about 7000 per indoor unit per year. The component only sends real changes, and each group has a write budget: 30 at once, one more every 75 minutes. Above that a command is refused and the entity springs back.
- Commands are queued 1.5 s apart and retried when the ATmega reports a collision.
Keep automations frugal: one that changes a setpoint every 10 minutes uses a year's budget in two to three months. docs/writing.md has the details, and how this works next to an iTM or wired remotes.
The stock firmware can program the ATmega over the network. So can this component: turn on ATmega programming and run avrdude against the bridge.
avrdude -c avrisp -P net:<bridge-ip>:328 -p m328p -U flash:w:P1P2Monitor-v0.9.58-Daikin-F1F2.ino.hex:iThe port only listens for 10 minutes after you turn the switch on. See docs/atmega.md.
F1F2 bus ── ATmega (P1P2Monitor) ──UART 250000── ESP8266 (ESPHome, daikin_diii)
├─ native API → Home Assistant
└─ raw MQTT (optional) → P1P2/{R,E,X}/P1P2MQTT/<bridge>
- P1P2Monitor prints every bus frame as a text line. The component reads those lines, checks length and checksum and decodes the frame types it knows (docs/protocol.md).
- Indoor units report their status in
F5frames: right away on a change, and about once a minute in full. Temperatures come from these and fromB1frames, outdoor data fromE9pages. - A command is an
A5frame to the group master. The bus has no read-back of a command, so the component shows the commanded value until the next status frame confirms it, at most about a minute later. - With
raw_mqtt, every frame is also published to MQTT in the stock P1P2MQTT format (R= bus frames,E= errors,X= frames this bridge wrote), so you can log the bus and use the tools in tools/. - Frame logging writes every frame to the ESPHome log instead, so you can make a bus log without MQTT. Unknown frame notifications puts a notification in Home Assistant the first time the bridge sees a frame type it doesn't know. See docs/debugging.md.
- Worked out on one system: a VRV IV heat recovery outdoor unit (REYQ10T) with 16 indoor units in 7 groups, a hydrobox and an iTM. Other systems may use frame types or values this component doesn't know. The component ignores them. If you have another Daikin system, I'd like to help get it working: docs/debugging.md shows how to make a bus log and a survey for a New system report.
- Several sensors are hypotheses: discharge temperature, compressor speed and current, compressor and fan steps, defrost. The protocol notes mark what is confirmed and what isn't.
- Auto and dry can't be set: their command codes are untested.
- Setpoints are whole degrees.
- The outlet selects are write-only. The units don't report the per-outlet setting on F1F2, so the select shows what this bridge last sent, and a change on the wired remote isn't seen. Only pairs of opposite outlets can be set, only to Normal or Fixed (0), and only the effect on a group master has been confirmed.
- Malfunction codes are not decoded yet: no unit has been in fault while logging.
- The hydrobox's water setpoint can't be set, and cool hasn't been tried on a hydrobox. The hydrobox doesn't report its mode, so the climate shows heat while it's on until this bridge sends cool.
- An iTM marks a unit switched off by another controller as setback; switching it on and off once from the iTM clears that.
- Only tested on the P1P2MQTT bridge v1.2/v1.3 with an ESP8266.
Host tests need a C++17 compiler and make:
make -C tests testunits: write guards, checksum, queue spacing and retries, the write budget over a simulated year, and decoder values checked by hand against real frames.isp: the ATmega programmer, a full avrdude-style session against a simulated ATmega328P.decoder: the C++ decoder against the Python reference over a 12-minute bus log in tests/fixtures/ and your own logs in captures/.
The tools have their own tests (Python 3.10 or newer, no packages needed): the log
converter, the survey, and a check that the firmware's list of known frame types matches
tools/find_unknown.py.
python3 -m unittest discover -s tests -p 'test_*.py'example.yaml loads everything from GitHub. To build your local changes, write a copy
that uses this checkout, with the hydrobox package turned on as well:
python3 tests/local_example.py build/ci
esphome compile build/ci/example.yamlCI (.github/workflows/ci.yml) runs the host tests and that build on every push and pull request.
The Python tools for logging and analysing the bus are in tools/ (docs/protocol.md explains how they were used):
| Script | What it does |
|---|---|
f1f2_log.py |
Log raw frames from MQTT to a TSV file, with notes typed on stdin. |
esphome_log_to_tsv.py |
Turn an ESPHome log with Frame logging on into a TSV bus log. No dependencies. |
survey.py |
Units, likely groups and B1 indexes, frame types and a packages list from a bus log. No dependencies. |
f1f2_decode.py |
Decode a log or the live stream into a table per unit. |
f1f2_experiment.py |
Change-and-restore experiments: Home Assistant service calls or raw frames, logged, with a restore at the end. |
analyse_diff.py, analyse_e9.py, find_unknown.py |
Find changed bytes, outdoor-unit fields, and frame types not described yet. |
cd tools && pipenv install
pipenv run python f1f2_decode.py ../captures/my-log.tsvContributions are welcome, especially bus logs from other systems and anything that confirms or corrects a hypothesis in docs/protocol.md.
Running a different Daikin system? I'm happy to help add support for it. Make a bus log and a survey as in docs/debugging.md and open a New system report; we can work out the rest together in the issue.
- P1P2MQTT by Arnold Niessen: the bridge hardware and the P1P2Monitor firmware this component talks to. Its firmware and hardware design are licensed CC BY-NC-ND 4.0 and are not part of this repository; download the firmware images from that project.
The component and tools are written from scratch, from the documented P1P2Monitor serial line format and the protocol notes in this repository. They contain no P1P2MQTT code.
Claude, Anthropic's AI assistant, was used to assist during the creation of the component, the tools and the documentation.
CC BY-NC-ND 4.0: free for personal use, and you may share it unmodified and non-commercially, with attribution. Commercial use and distributing modified versions are not allowed.